Ball & Socket coupling LXDP-120

Ball & Socket coupling LXDP-120

Dimensions:

Diameter (D): 12 5/8 inch (320mm)

Spacing (H): 5 3/4 inch (146mm)

Leakage Distance: 19 11/16 inch (500mm)


Mechanical Values:

Mechanical Failing Load: 25,000 Pounds (120kN)

Tension Proof: 12,500 Pounds (60kN)


Electrical Values:

Low Frequency Dry Flashover Voltage: 95kV

Low Frequency Wet Flashover Voltage: 60kV

Critical Impulse Flashover Voltage, Positive: 140kV

Critical Impulse Flashover Voltage, Negative: 140kV

Low Frequency Puncture Voltage: 130kV


Radio Influence Voltage Data:

Test Voltage RMS to Ground: 10kV

Maximum RIV at 1000 kHz: 50μV


Packing and Shipping Data:

Net Weight, Approximate: 6.4kg